How to Choose a Server Rack Sizes, Width, Depth & Load Rating Explained
Shop server racks →Colocation racksNetwork cabinets
Choosing the wrong server rack is an expensive mistake: equipment that will not fit, cables with nowhere to go, hot spots and a rack full two years early. This guide explains how to choose a server rack by height, width, depth and load rating, and how to match it to your power, cooling and cable management.
Shop server racks & data centre cabinets
Order online for UK delivery from Telenco UK
Shop server racks →Colocation racksAisle containmentRack PDUsRack accessories
A server rack (or server cabinet) is a steel enclosure with 19-inch mounting rails for servers, storage, switches and power equipment. It is defined by four things: usable height in rack units (U), external width, external depth and load rating. Server racks normally have perforated front and rear doors so cool air can pass front-to-back through the equipment.
Server Rack Sizes: 42U vs 47U vs 52U
Rack height is measured in rack units. 1U is 44.45 mm (1.75 inches), the height of a standard 1U server, as defined by the EIA-310 / IEC 60297 19-inch standard. A 42U rack therefore gives about 1.87 m of usable mounting space.
| Height | Usable space | Best for |
|---|---|---|
| 42U | ≈1.87 m | The industry standard. Fits most rooms, doors and lifts and suits most enterprise and comms rooms. |
| 47U | ≈2.09 m | Data centre halls where floor space costs more than height. Five extra U per rack adds up across a row. |
| 52U | ≈2.31 m | Maximum density in halls with high ceilings and overhead containment designed around tall racks. |
Before choosing a taller rack, check the clear ceiling height under any overhead cable containment, sprinklers and lighting, and the height of every door and lift on the delivery route.
Server Rack Width: 600 mm, 800 mm or 1000 mm?
600 mm wide
The densest option: equipment fills almost the full width, so you fit the most racks per row. Best for compute and storage racks with modest cabling. RACKEON® 42U 600 mm.
800 mm wide
Adds about 100 mm each side of the 19-inch rails for vertical cable managers and 0U PDUs. The most popular all-round choice for network, top-of-rack switching and mixed racks. RACKEON® 47U 800 mm.
1000 mm wide
For very high cable counts, core switching and patching-heavy racks where large bundles must run vertically. RACKEON® 42U 1000 mm.
Server Rack Depth: 1000 mm vs 1200 mm
Depth is where most projects go wrong. Modern 1U and 2U servers are commonly 750 to 900 mm deep, and they need space behind them for power cords, cable arms and rear-mounted PDUs. As a rule of thumb, allow at least 150 to 200 mm behind your deepest device.
- 1200 mm deep is the safe default for data centre server racks, and every RACKEON® server rack is 1200 mm deep.
- 1000 mm deep suits shorter equipment and rooms where aisle space is tight, for example the RAINFORD® 47U 800 × 1000 mm server rack. A 1200 mm deep RAINFORD® version is also available.
- Leave at least 1.2 m clear in front of and behind each row for installation and maintenance.
Server Rack Load Rating
Add up the fully populated weight, not the day-one weight: servers, storage arrays, UPS modules, PDUs, shelves and cabling. A fully loaded 47U rack can easily exceed 800 kg. All RACKEON® server racks are rated to 1500 kg.
Static load is what the rack holds standing on its feet. If you need to move racks after loading, check the dynamic rating of the castors as well: our metal server rack castors are rated to a 1500 kg dynamic load. Always check the floor loading of raised floors with your structural engineer.
Server Rack vs Network Cabinet vs Colocation Rack
| Type | Typical size | Use it for |
|---|---|---|
| Server rack | 42–52U, 600–1000 mm wide, 1000–1200 mm deep | Servers, storage and heavy equipment in data centres and server rooms |
| Network / comms cabinet | Wall mount or floor standing, shallower | Switches, patch panels and small servers in offices and comms rooms |
| Colocation rack | 47U with 2, 3 or 4 lockable compartments | Multi-tenant data centres where several customers share one rack |
Not sure which you need? Our data centre racks & containment hub groups every rack type with the containment, cooling and power that goes with it.
Airflow, Containment and Cooling
Server racks are designed for front-to-back airflow: cold air in through the perforated front door, hot air out at the rear. To keep it that way, fit blanking panels in every empty U and use airflow separation frames to stop hot air recirculating around the rails.
At row level, hot or cold aisle containment separates supply and exhaust air, and higher-density racks may need rear door or in-row cooling. Read our guide to hot vs cold aisle containment.
Power and Accessories
Plan power at the same time as the rack. Vertical 0U PDUs mount in the side space of 800 mm racks, while 1U PDUs use rack space. See what is a PDU? and metered vs switched PDUs, or shop rack PDUs.
Shelves, cable guides, side panels, castors and grounding kits finish the rack. Our server rack accessories guide explains what each one does.
Server Rack Selection Checklist
Count your U
List every device, add 30–50% for growth, PDUs and cable management.
Check the room
Ceiling height, doors, lifts, floor loading and aisle widths.
Choose width
600 mm for density, 800 mm for cabling and 0U PDUs, 1000 mm for very high cable counts.
Choose depth
Deepest device plus 150–200 mm; 1200 mm for most data centres.
Confirm load
Fully populated weight, with castors rated for any moves.
Plan power and cooling
PDUs, blanking, airflow separation and aisle containment.
Server Rack FAQs
What size server rack do I need?
Count the rack units (U) of all your equipment, add 30 to 50% for growth, PDUs and cable management, and choose the next standard height up: 42U, 47U or 52U. Then pick a width (600, 800 or 1000 mm) for your cabling density and a depth (usually 1200 mm for modern servers) that leaves room behind the deepest device.
How tall is a 42U rack?
42U is the usable mounting height: 42 × 44.45 mm, or about 1.87 m of 19-inch mounting space. The overall cabinet is taller once the roof, plinth and castors or feet are added, so check the external height on the product page against your door openings and ceiling.
What is the difference between a server rack and a network cabinet?
A server rack is usually deeper (1000 to 1200 mm), built for heavy loads and has perforated doors for front-to-back airflow. A network or comms cabinet is often shallower, may be wall mounted and is designed for switches, patch panels and light equipment.
Should I choose a 600 mm or 800 mm wide server rack?
600 mm wide racks give the densest row and suit servers and storage with modest cabling. 800 mm wide racks add space each side for vertical cable management and 0U PDUs, which suits network, top-of-rack switching and high-density patching.
What load rating does a server rack need?
Add up the fully populated weight: servers, storage, UPS, PDUs and cabling. Choose a rack with a static load comfortably above that figure, and if the rack will be moved while loaded, check the dynamic load of the castors too. RACKEON® server racks are rated to 1500 kg.
Need help specifying racks?
Telenco UK supplies RACKEON® and RAINFORD® server racks, colocation racks, aisle containment, cooling, rack PDUs and accessories for UK data centres and server rooms.